# Communication
Nome parametro | Descrizione dei parametri | Intervallo dei parametri |
---|---|---|
Server Address | The data communication transmission address of the collector. | |
Server Port | The service transmission port for data communication of the collector. | |
Collector system time | Set according to the actual time in the country/region where the device is located |
# Grid parameters
Nome parametro | Descrizione dei parametri | Intervallo dei parametri |
---|---|---|
Country | Please select the national/regional power grid standards supported by the device based on the country/region where the device is located. | |
Statute | The specific standards supported by the device under the national/regional power grid should be selected based on the current grid standards connected to the device. |
# Protection
Nome parametro | Descrizione dei parametri | Intervallo dei parametri |
---|---|---|
AC startup high voltage (V) | Threshold for overvoltage judgment of power grid before grid connection | 100V-600V,Minimum unit 0.1V |
AC Start Low Voltage (V) | Threshold for undervoltage judgment of power grid before grid connection | 45Hz-65Hz,Minimum unit 0.01Hz |
AC startup high-frequency (Hz) | Threshold for determining grid overclocking before grid connection | 100V-600V,Minimum unit 0.1V |
AC Start Low Frequency (Hz) | Threshold for underfrequency judgment of power grid before grid connection | 45Hz-65Hz,Minimum unit 0.01Hz |
10 minute overvoltage protection | Overvoltage protection function switch | Enable/Disable |
10 minute overvoltage protection value (V) | Protection threshold | Minimum unit 0.1V |
10 minute overvoltage recovery value (V) | Recovery threshold | Minimum unit 0.1V |
Protection level(V) | Set the grid protection level of the device | Level 1 Level 2 Level 3 Level 4 Level 5 |
Undervoltage 1 level protection value (V) | First level undervoltage protection threshold | Minimum unit 0.1V |
Overvoltage 1 level protection value (V) | First level overvoltage protection threshold | Minimum unit 0.1V |
Under frequency 1 level protection value (Hz) | First level underfrequency protection threshold | Minimum setting 0.01Hz |
Overfrequency 1 level protection value (Hz) | First level overclocking protection threshold | Minimum setting 0.01Hz |
Under voltage 1 level protection time (ms) | First level undervoltage protection triggering judgment time | Minimum setting 20ms |
Overvoltage 1 level protection time (ms) | First level overvoltage protection triggering judgment time | Minimum setting20ms |
Under frequency 1 level protection time (ms) | First level underfrequency protection triggering judgment time | Minimum setting20ms |
Overfrequency 1 level protection time (ms) | First level overclocking protection triggering judgment time | Minimum setting20ms |
Undervoltage 2 level protection value (V) | Second level undervoltage protection threshold | Minimum unit 0.1V |
Overvoltage 2 level protection value (V) | Second level overvoltage protection threshold | Minimum unit 0.1V |
Under frequency 2 level protection value (Hz) | Second level underfrequency protection threshold | Minimum setting0.01Hz |
Overfrequency 2 level protection value (Hz) | Second level overclocking protection threshold | Minimum setting0.01Hz |
Under voltage 2 level protection time (ms) | Second level undervoltage protection triggering judgment time | Minimum setting20ms |
Overvoltage 2 level protection time (ms) | Second level overvoltage protection triggering judgment time | Minimum setting20ms |
Under frequency 2 level protection time (ms) | Second level underfrequency protection triggering judgment time | Minimum setting20ms |
Overfrequency 2 level protection time (ms) | Second level overclocking protection triggering judgment time | Minimum setting20ms |
Undervoltage 3 level protection value (V) | Third level undervoltage protection threshold | Minimum unit 0.1V |
Overvoltage 3 level protection value (V) | Third level overvoltage protection threshold | Minimum unit 0.1V |
Under frequency 3 level protection value (Hz) | Third level underfrequency protection threshold | Minimum setting0.01Hz |
Overfrequency 3 level protection value (Hz) | Third level overclocking protection threshold | Minimum setting0.01Hz |
Under voltage 3 level protection time (ms) | Third level undervoltage protection triggering judgment time | Minimum setting20ms |
Overvoltage 3 level protection time (ms) | Third level overvoltage protection triggering judgment time | Minimum setting20ms |
Under frequency 3 level protection time (ms) | Third level underfrequency protection triggering judgment time | Minimum setting20ms |
Overfrequency 3 level protection time (ms) | Third level overclocking protection triggering judgment time | Minimum setting20ms |
Undervoltage 4 level protection value (V) | Fourth level undervoltage protection threshold | Minimum unit 0.1V |
Overvoltage 4 level protection value (V) | Fourth level overvoltage protection threshold | Minimum unit 0.1V |
Under frequency 4 level protection value (Hz) | Fourth level underfrequency protection threshold | Minimum setting0.01Hz |
Overfrequency 4 level protection value (Hz) | Fourth level overclocking protection threshold | Minimum setting0.01Hz |
Under voltage 4 level protection time (ms) | Fourth level undervoltage protection triggering judgment time | Minimum setting20ms |
Overvoltage 4 level protection time (ms) | Time for triggering and judging the fourth level overvoltage protection | Minimum setting20ms |
Under frequency 4 level protection time (ms) | Fourth level underfrequency protection triggering judgment time | Minimum setting20ms |
Overfrequency 4 level protection time (ms)/td> | Fourth level overclocking protection trigger judgment time | Minimum setting20ms |
Undervoltage 5 level protection value (V) | Five level undervoltage protection threshold | Minimum unit 0.1V |
Overvoltage 5 level protection value (V) | Five level overvoltage protection threshold | Minimum unit 0.1V |
Under frequency 5 level protection value (Hz) | Five level underfrequency protection threshold | Minimum setting0.01Hz |
Overfrequency 5 level protection value (Hz) | Five level overclocking protection threshold | Minimum setting0.01Hz |
Under voltage 5 level protection time (ms) | Five level undervoltage protection triggering judgment time | Minimum setting20ms |
Overvoltage 5 level protection time (ms) | Five level overvoltage protection triggering judgment time | Minimum setting20ms |
Under frequency 5 level protection time (ms) | Five level underfrequency protection triggering judgment time | Minimum setting20ms |
Overfrequency 5 level protection time (ms) | Five level overclocking protection trigger judgment time | Minimum setting20ms |
# Characteristic
Nome parametro | Descrizione dei parametri | Intervallo dei parametri |
---|---|---|
Grid connected operation switch | Control whether the equipment is connected to the grid, set it to "enable", and the equipment will start grid connected operation. | Enable/Disable |
anti-reflux | When it is necessary to limit the output power according to the grid standards of certain countries/regions, turn on this function. | Enable/Disable |
Permissible countercurrent power (kW) | The first level allows for the triggering and judgment time of reverse power protection | 0-6553.5kW,The smallest unit0.1kW |
Restricting countercurrent methods | Choose the method of limiting device power, and before setting it, please confirm whether the device supports this method. | Limit three-phase total power/limit individual power |
Fault protection active power limit (kW) | When there is an abnormal communication between the online electricity meter and the inverter, the active power limit of the inverter can be manually adjusted by the customer as needed. | 0-6553.5kW,The smallest unit0.1kW |
Communication broken chain detection time (s) | Set the detection time for communication disconnection failure protection between the inverter and the data stick. | Minimum unit 1s,highest 65535s |
DCI | DC component protection switch | Enable/Disable |
GFCI | Residual current protection switch | Enable/Disable |
ISO | Insulation impedance protection switch | Enable/Disable |
Virtual N-line enable | Suitable for three-phase three wire system or three-phase four wire system. | Do not enable (three-phase four wire)/Enable (three-phase three wire) |
ISO protection value(kOhm) | Insulation impedance protection value | Minimum 10kOhm, maximum 1000kOhm |
DCI protection value(mA) | DC component protection value。 | Minimum 1ms, maximum 50000ms |
DCI protection time(s) | DC component protection time, triggering DC component | Minimum 1 second, maximum 60000 seconds. |
PV connection method | Independent parallel DC source mode selection | independent parallel connection DC Source mode |
Parallel enabling | According to the requirements of certain countries or regions, this function needs to be enabled when a three-phase parallel system is composed of three single-phase inverters. Multiple low-power devices can also be used to drive higher power loads by enabling this function. | Enable/Disable |
Master slave settings | • Choose whether the current connected device is a host or a slave based on the actual situation. • The device connected to the R phase is the master, and the device connected to the S or T phase is the slave. | Enable/Disable |
Parallel phase setting | Parallel phase relationship setting | R-phase/S-phase/T-phase |
Energy distribution mode | Set the operating mode of the device | Off grid mode/UPS mode/Self use mode/Peak shaving and valley filling mode |
Slave address | Connect to the communication address of the upper computer | |
Baud rate | Communication speed connected to the upper computer |
# Battery
Nome parametro | Descrizione dei parametri | Intervallo dei parametri |
---|---|---|
Battery type | Select the type of battery | No/Lead acid battery/Lithium battery |
Battery operation type | Selection of battery working mode | According to voltage/according to SOC/without battery |
Number of batteries in series and parallel | Number of battery packs | |
Battery manufacturer | Set the manufacturer of the battery。 | Zhongxing Paineng_CAN Zhongxing Paineng_RS485 Tianbang Da_CAN Tianbang Da_RS485 Xinwangda_CAN Xinwangda_RS485 BYD_CAN BYD_RS485 Youneng_CAN Youneng_RS485 Jiabaida_CAN Jiabaida_RS485 AOBOET_CAN AOBOET_RS485 SLENERGY_CAN SLENERGY_RS485 DESAY_CAN DESAY_RS485 GENIXGEREEN_CAN GENIXGEREEN_RS485 DYNESS_CAN DYNESS_RS485 |
Charge cutoff SOC (%) | Set the charging cut-off capacity。 | 0 to 100% |
Discharge cut-off SOC (%) | Set discharge cut-off capacity。 | 0 to 100% |
Enable grid charging | When the default setting for 'grid charging' is' not enabled 'at the factory, it is allowed to purchase electricity from the grid after enabling it. If users enable this function, they must comply with local regulations for grid charging. | Enable/Disable |
SOC for grid charging start-up (%) | Set the starting capacity for grid charging. | 0 to 100% |
Grid charging stop SOC (%) | Set the cut-off capacity for grid charging. | 0 to 100% |
Selling electricity settings | The switch that controls the device to start selling electricity to the inverter。 | Enable/Disable |
AC charging power(kW) | The power used to charge batteries from the power grid。 | Minimum setting unit 0.1kW |
AC charging target voltage(V) | Target voltage for charging batteries from the power grid。 | Minimum setting unit 0.1V |
AC charging target SOC | Target SOC for charging batteries from the power grid。 | unit1% |
AC charging current | The current used to charge batteries from the power grid。 | unit1A |
Charging and discharging time setting | Set the switch for automatic battery charging and discharging, linked with the "time point setting" parameter, and hide the "time point setting" parameter when "not enabled". | |
Time point setting | Set specific conditions and work efficiency for automatic charging and discharging of batteries. | |
AC charging time period | Set the time period and charging power for automatic AC charging of energy storage devices. | |
Forced charging and discharging settings | Set the start time, work efficiency, and start conditions for forced charging and discharging of the battery. | |
Off grid output time period setting | Set up a critical load work plan for the equipment. | |
Battery charging power (kW) | Set the charging power of the energy storage device。 | Minimum 0, maximum 6553.5kW,unit0.1kW |
Battery discharge power (kW) | Set the discharge power of the energy storage device。 | Minimum 0, maximum 6553.5kW,unit0.1kW |
# Charging and discharging time setting
Nome parametro | Descrizione dei parametri | Intervallo dei parametri |
---|---|---|
Start End Time | The start/end time of battery charging and discharging | |
Maximum discharge power (kW) | Maximum working power of battery discharge | minimum0.1kW |
Start charging SOC value (%) | When the SOC value of the battery reaches the set value, charging begins | Minimum setting unit 1% |
Starting charging voltage(V) | When the battery voltage reaches the set value, charging begins. | Minimum setting unit 0.1V |
Type | Energy source during charging。 | Power grid/generator |
# AC charging time period
Nome parametro | Descrizione dei parametri | Intervallo dei parametri |
---|---|---|
Start End Time | The time when the battery starts/ends charging and discharging. | |
Charging power (kW) | Working power of battery discharge | minimum0.1kW |
Charge cutoff SOC (%) | Stop charging when the battery SOC value reaches the set value | Minimum setting unit 1% |
Charging cut-off voltage (V) | When the battery voltage reaches the set value, charging begins. | Minimum setting unit 0.1V |
# Forced charging and discharging settings
Parameter Name | Descrizione dei parametri | Intervallo dei parametri |
---|---|---|
Start End Time | The time when the battery is forced to start and end charging and discharging。 | |
Charging power (kW) | Output power during battery discharge | minimum0.1kW |
Charging cut-off SOC value (%) | When the SOC value of the battery reaches the set value, charging begins | Minimum setting unit 1% |
Charging cut-off voltage (V) | Stop charging when the battery voltage reaches the set value. | Minimum setting unit 0.1V |
Discharge power (kW) | Output power during battery discharge | minimum0.1kW |
Discharge cut-off SOC value (%) | When the SOC value of the battery reaches the set value, discharge begins | Minimum setting unit 1% |
Discharge cut-off voltage (V) | Stop discharging when the battery voltage reaches the set value。 | Minimum setting unit 0.1V |
# Off grid output time period setting
Parameter Name | Descrizione dei parametri | Intervallo dei parametri |
---|---|---|
Start and endtime | The start/end time of battery off grid output. |
# Off-grid
Nome parametro | Descrizione dei parametri | Intervallo dei parametri |
---|---|---|
Start End Time | Off grid operation switch。 | Enable/Disable |
Off grid output voltage (V) | Critical load supply voltage.. | 208V/220V/230V/240V |
Off grid output frequency (Hz) | Critical load power supply frequency. | 50Hz/60Hz |
# Energy
Nome parametro | Descrizione dei parametri | Intervallo dei parametri |
---|---|---|
UPS mode | Set the battery operating mode to UPS mode. | Enable/Disable |
Peaking shift mode | The working mode of the device battery is peak shaving and valley filling mode. | Enable/Disable |
AC power measurement method | Choose the AC side power measurement method. | No/electricity meter/wired CT |
Electricity meter enable | Select the electric meter metering switch. | Enable/Disable |
Electricity meter type | Select the type of electricity meter | Single phase/Three phase |
Electric meter brand and agreement | Set the brand and corresponding communication protocol of the electricity meter | CAN/RS485 |
R phase external CT enable | Select R-phase external CT operation. | Enable/Disable |
S phase external CT enable | Select S-phase external CT operation. | Enable/Disable |
T phase external CT enable | Select T-phase external CT operation. | Enable/Disable |
R Phase CT direction setting | Current direction setting of R-phase current transformer。 | Normal (default)/Reverse |
S Phase CT direction setting | Current direction setting of S-phase current transformer。 | Normal (default)/Reverse |
T Phase CT direction setting | Current direction setting of T-phase current transformer。 | Normal (default)/Reverse |
CT self check direction enable | Automatic detection switch for current direction of current transformer。 | Enable(default)/Disable |
External CT changes | The ratio of the current magnitude on both sides of the current transformer。 | 1-5000,default 1000 |