# Equipment configuration

  This system supports reading or setting device operating parameters in the data list of the device module.

# Global configuration steps

① Log in to the Smart M app.

② Click on [Device] at the bottom to enter the data list page.

③ Click the [...] - [Configure] button on the right side. (If the device model supports quick configuration, clicking the configuration button will bring up a configuration mode selection pop-up window. If quick configuration is not supported, the page will directly enter the parameter configuration page.)

④ Select Global Configuration in the pop-up configuration mode selection window.

⑤ In the pop-up parameter configuration page, select the type of parameter that needs to be set.

⑥ In the corresponding parameter type input box, enter the parameter value that needs to be modified, and click the [Settings] button.

# Communication

Parameter NameParameter DescriptionParameter Range
Server address The data communication transmission address of the collector.
Server Port The service transmission port for data communication of the collector.
Collector system time Set according to the actual time in the country/region where the device is located

# Grid

Parameter NameParameter DescriptionParameter Range
Country Setting different countries, regulations will display corresponding content
Standard After setting regulations, relevant information such as grid connection parameters, protection&time, etc. will be automatically modified to the corresponding regulatory settings.
Auto Test Used to check and verify the operational status, performance, and safety of inverters. When choosing Italy as the country, the Auto Test function can be used

# On-Grid

On-Grid conditions

Parameter NameParameter DescriptionParameter Range
AC HV start (V) The highest mains voltage that a machine can connect to the grid. If the machine detects that the mains voltage exceeds this voltage before grid connection, it will not be able to connect to the grid (the regulations will be automatically modified to the corresponding regulatory settings, and it is not recommended for users to modify) 100V-600V,minimum unit 0.1V
AC LV start (V) The minimum mains voltage at which a machine can connect to the grid. If the machine detects that the mains voltage is lower than this voltage before grid connection, it will not be able to connect to the grid (the regulations will be automatically modified to the corresponding regulatory settings, and it is not recommended for users to modify) 100V-600V,minimum unit 0.1V
AC HF start (Hz) The highest mains frequency at which a machine can connect to the grid. If the machine detects that the mains frequency exceeds this frequency before grid connection, it will not be able to connect to the grid (the regulations will be automatically modified to the corresponding regulatory settings, and it is not recommended for users to modify) 45Hz-65Hz,minimum unit 0.01Hz
AC LF start (Hz) The minimum mains frequency at which a machine can connect to the grid. If the machine detects that the mains voltage is lower than this frequency before grid connection, it will not be able to connect to the grid (the regulations will be automatically modified to the corresponding regulatory settings, and it is not recommended for users to modify) 45Hz-65Hz,minimum unit 0.01Hz
Connection Waiting Time (s) The waiting time before the first grid connection after the machine is turned on (setting regulations will automatically modify to the corresponding regulatory settings, and it is not recommended for users to modify) 1-65535s, minimum 1s
Reconnect Time (s) The waiting time before the machine is reconnected to the grid due to standby or disconnection from the mains power, etc. (The setting of regulations will automatically modify to the corresponding regulatory setting value, and it is not recommended for users to modify it) 1-65535s, minimum 1s
First connect upward slope (% Pn/min) The rate at which the machine tracks to the maximum power point of MPPT after being connected to the grid for the first time after startup (the setting of regulations will automatically modify to the corresponding regulatory setting value, and it is not recommended for users to modify it) 1-65535,minimum unit 1X%Pn/min
Reconnect upward slope (% Pn/min) The rate at which the machine tracks to the maximum power point of MPPT after reconnecting to the grid (setting regulations will automatically modify to the corresponding regulatory setting value, it is not recommended for users to modify) 1-65535,minimum unit 1X%Pn/min
LVRT Enable Enable low voltage ride through function after activation Open/Close
HVRT Enable Enable high voltage ride through function after activation Open/Close
Zero current ride through enable Enable zero current ride through function after activation Open/Close

Protection & Time

Parameter NameParameter DescriptionParameter Range
UV1 (V) When the machine detects that the mains voltage is too low, it will protect and report a level 1 undervoltage fault (the setting regulations will automatically modify to the corresponding regulatory setting values, and it is not recommended for users to modify) Minimum setting 0, minimum unit 0.1V
OV1(V) When the machine detects that the mains voltage is too high, it will protect and report a level 1 overvoltage fault (the setting regulations will automatically modify to the corresponding regulatory setting values, and it is not recommended for users to modify) Minimum setting 0, minimum unit 0.1V
UF1(Hz) When the machine detects that the mains frequency is low to this frequency, it will protect and report a level 1 underfrequency fault (setting regulations will automatically modify to the corresponding regulatory setting value, it is not recommended for users to modify) Minimum setting 0, minimum unit 0.01Hz
OF1(Hz) When the machine detects that the mains frequency is too high at this frequency, it will protect and report a level 1 overclocking fault (setting regulations will automatically modify to the corresponding regulatory setting value, it is not recommended for users to modify) Minimum setting 0, minimum unit 0.01Hz
UV1_T(ms) The time taken from level 1 undervoltage of the mains power to machine protection (setting regulations will automatically modify to the corresponding regulatory setting value, it is not recommended for users to modify) Minimum setting 0, minimum unit 20ms
OV1_T(ms) The time taken from level 1 overvoltage of the mains power to machine protection (the setting of regulations will automatically modify to the corresponding regulatory setting value, and it is not recommended for users to modify) Minimum setting 0, minimum unit 20ms
UF1_T(ms) The time taken from underfrequency at level 1 of the municipal power supply to machine protection (setting regulations will automatically modify to the corresponding regulatory settings, and it is not recommended for users to modify) Minimum setting 0, minimum unit 20ms
OF1_T(ms) The time taken from level 1 overclocking of the mains power to machine protection (setting regulations will automatically modify to the corresponding regulatory setting value, and it is not recommended for users to modify) Minimum setting 0, minimum unit 20ms
UV2(V) When the machine detects that the mains voltage is too low, it will protect and report a level 2 undervoltage fault (the setting regulations will automatically modify to the corresponding regulatory setting values, and it is not recommended for users to modify) Minimum setting 0, minimum unit 0.1V
OV2(V) When the machine detects that the mains voltage is high enough, it will protect and report a level 2 overvoltage fault (the setting regulations will automatically modify to the corresponding regulatory setting values, and it is not recommended for users to modify) Minimum setting 0, minimum unit 0.1V
UF2(Hz) When the machine detects that the mains frequency is low to this frequency, it will protect and report a level 2 underfrequency fault (setting regulations will automatically modify to the corresponding regulatory setting value, it is not recommended for users to modify) Minimum setting 0, minimum unit 0.01Hz
OF2(Hz) When the machine detects that the mains frequency is too high at this frequency, it will protect and report a level 2 overclocking fault (setting regulations will automatically modify to the corresponding regulatory setting value, it is not recommended for users to modify) Minimum setting 0, minimum unit 0.01Hz
UV2_T(ms) The time taken from under voltage at level 2 of the mains power supply to machine protection (the setting of regulations will automatically modify to the corresponding regulatory setting value, and it is not recommended for users to modify it) Minimum setting 0, minimum unit 20ms
OV2_T(ms) The time taken from overvoltage level 2 of the mains power to machine protection (setting regulations will automatically modify to the corresponding regulatory setting value, it is not recommended for users to modify) Minimum setting 0, minimum unit 20ms
UF2_T(ms) The time taken from underfrequency at level 2 of the mains power to machine protection (setting regulations will automatically modify to the corresponding regulatory settings, and it is not recommended for users to modify) Minimum setting 0, minimum unit 20ms
OF2_T(ms) The time taken from overclocking at level 2 of the mains power to machine protection (setting regulations will automatically modify to the corresponding regulatory settings, and it is not recommended for users to modify) Minimum setting 0, minimum unit 20ms
UV3(V) When the machine detects that the mains voltage is too low, it will protect and report a level 3 undervoltage fault (the setting regulations will automatically modify to the corresponding regulatory setting values, and it is not recommended for users to modify) Minimum setting 0, minimum unit 0.1V
OV3(V) When the machine detects that the mains voltage is high enough, it will protect and report a level 3 overvoltage fault (the setting regulations will automatically modify to the corresponding regulatory setting values, and it is not recommended for users to modify) Minimum setting 0, minimum unit 0.1V
UF3(Hz) When the machine detects that the mains frequency is low to this frequency, it will protect and report a level 3 underfrequency fault (setting regulations will automatically modify to the corresponding regulatory setting value, it is not recommended for users to modify) Minimum setting 0, minimum unit 0.01Hz
OF3(Hz) The machine detects that the mains frequency is too high and will protect it, reporting a level 3 overclocking fault (setting regulations will automatically modify to the corresponding regulatory setting value, it is not recommended for users to modify) Minimum setting 0, minimum unit 0.01Hz
UV3_T(ms) The time taken from level 3 undervoltage of the mains power to machine protection (setting regulations will automatically modify to the corresponding regulatory setting value, it is not recommended for users to modify) Minimum setting 0, minimum unit 20ms
OV3_T(ms) The time taken from level 3 overvoltage of the mains power to machine protection (setting regulations will automatically modify to the corresponding regulatory setting value, and it is not recommended for users to modify) Minimum setting 0, minimum unit 20ms
UF3_T(ms) The time taken from underfrequency at level 3 of the mains power to machine protection (setting regulations will automatically modify to the corresponding regulatory settings, and it is not recommended for users to modify) Minimum setting 0, minimum unit 20ms
OF3_T(ms) The time taken from overclocking at level 3 of the mains power to machine protection (setting regulations will automatically modify to the corresponding regulatory settings, and it is not recommended for users to modify) Minimum setting 0, minimum unit 20ms
10 min OV Protection(V) When the grid voltage exceeds 1.1 times, the inverter should operate for at least 10 minutes (conflicting with the overvoltage protection function, which requires setting the overvoltage protection time to be greater than 10 minutes) Minimum setting 0, minimum unit 0.1V

Power

Parameter NameParameter DescriptionParameter Range
Active power % After setting the value, the maximum power of the machine becomes the maximum power multiplied by the set percentage Minimum setting 0, minimum unit 0.1%
P(U) Curve Enable After setting, the machine works according to the P (U) curve Open/Close
V1 (V) After setting the value, the equipment adjusts to the voltage value after the power grid is overvoltage Minimum setting 0, minimum unit 0.1V
V1_P (%) After setting the value, the equipment adjusts the power to the value after overvoltage in the power grid Minimum setting 0, minimum unit 0.1%
T (s) After setting the value, the equipment will automatically adjust after experiencing the overvoltage of the power grid for a certain period of time Minimum setting 0, minimum unit 1s
Power response switch After enabling, the reactive power response speed can be set, otherwise it will respond at the fastest speed Open/Close
T (s) Set reactive power response time constant
Reactive regulation method The specific standards supported by the device under the national/regional power grid should be selected based on the current grid standards connected to the device. Disable
PE Enable
Reactive power % Enable
Q (U) curve can be set
Q (P) curve can be set
Reactive power % (%) Reactive power percentage can be set Minimum setting 0, minimum unit 0.1%
power factor Power factor value can be set Minimum setting 0, minimum unit 0.001
Q(P) Curve Type Q (P) curve can be set CurveA
CurveB
CurveC
Q(U) Curve Type Q (U) curve can be set CurveA
CurveB
CurveC

# Characteristic

Parameter NameParameter DescriptionParameter Range
PV Connect Independent parallel DC source mode selection MPPT Standalone
MPPT Parallel
DC Source
Anti-reverse current After turning on, the machine delivers energy to the mains side at the set power. Open/Close
Allowable reverse current power (kW) The first level allows for the triggering and judgment time of reverse power protection. 0-6553.5kW, minimum unit 0.1kW
Restricting countercurrent methods Choose the method of limiting device power, and before setting it, please confirm whether the device supports this method. Limit three-phase total power/limit individual power
DCI DCI stands for DC component, and when turned on, the machine will control the DC component on the grid side within the regulatory allowable range. Open/Close
GFCI Leakage current detection protection, the machine will protect when the leakage current exceeds the safe range Open/Close
ISO Insulation impedance testing, which will be conducted by the machine during grid connection testing after enabling. Open/Close
N-PE Check After turning on, the machine will check if the N-PE connection is normal, and if there are any abnormalities, it will sound an alarm. Open/Close
Zero ground relay enable When there is an abnormal communication between the online electricity meter and the inverter, the active power limit of the inverter can be manually adjusted by the customer as needed. Open/Close
Power grid restoration with gradual change in power Set the detection time for communication disconnection failure protection between the inverter and the data stick. Open/Close
Weak grid mode Suitable for three-phase three wire system or three-phase four wire system. Open/Close
Zero current mode After enabling, the machine can perform high and low voltage crossing at zero current. Open/Close
DC lightning protection detection DC component protection value. Open/Close
RCR RCR enabled, can control the percentage of active power when turned on Open/Close
Island After activation, the machine can quickly identify and exit the grid connection when it enters an isolated state Open/Close
DRM DRM enabled, can control the percentage of active power when turned on Open/Close
AFCI After enabling, the device starts arc detection Open/Close
Backup ON/OFF By default, it is turned off. After being turned on, the machine can back up for voltage output during the set off grid time period Open/Close
Backup time setting Communication speed connected to the upper computer
Offgrid Volt Setting (V) The off grid side output voltage can be modified. When the machine is off grid, the back up output is the off grid voltage setting value, and when connected to the grid, the back up output is the mains input voltage Minimum setting 0, minimum unit 0.1V
Offgrid Freq Setting (Hz) The off grid side output frequency can be modified. When the machine is off grid, the back up output is the off grid frequency setting value, and when connected to the grid, the back up output is the mains input frequency Minimum setting 0, minimum unit 0.01Hz
Parallel Enable parallel operation and disable single machine operation Open/Close
Parallel address No setting required, automatically retrieved from the device after enabling parallel operation
master-slave setup Choose whether the current connected device is a host or a slave based on the actual situation. Host/Slave

# Battery

Parameter NameParameter DescriptionParameter Range
Batt manufacturer Set the manufacturer of the battery Zhongxing Paineng_CAN
Zhongxing Paineng_RS485
Tianbang Da_CAN
Tianbang Da_RS485
Xinwangda_CAN
Xinwangda_RS485
BYD_CAN
BYD_RS485
Youneng_CAN
Youneng_RS485
Jiabaida_CAN
Jiabaida_RS485
AOBOET_CAN
AOBOET_RS485
SLENERGY_CAN
SLENERGY_RS485
DESAY_CAN
DESAY_RS485
GENIXGEREEN_CAN
GENIXGEREEN_RS485
DYNESS_CAN
DYNESS_RS485
Batt Type Select the type of battery No Batt/Lead-acid/Lithum
Battery operation type Select battery operating mode Voltage/SOC/No Batt
Discharge Cut-off Volt in Hybrid mode (V) In the presence of PV, after setting the value, the battery voltage will stop discharging when it is lower than the set value Minimum setting 0, minimum unit 0.1V
Discharge Cut-off SOC in Hybrid mode (%) In the presence of PV, after setting the value, the battery will discharge until the SOC is lower than the set value, and then stop discharging Minimum setting 0, minimum unit 1%
Recovery Volt in Hybrid mode (V) In the presence of PV, after setting the value, discharging is allowed when the battery voltage is higher than the set value Minimum setting 0, minimum unit 0.1V<
Recovery SOC in Hybrid mode (%) In the presence of PV, after setting the value, the battery is allowed to discharge after charging to SOC higher than the set value Minimum setting 0, minimum unit 1%
Max Discharge (A) Set the maximum discharge current of the battery Minimum setting 0, minimum unit 1A
Max Charge (A) Set the maximum charging current of the battery Minimum setting 0, minimum unit 1A
Charge Power (kW) Set the maximum charging power of the battery Minimum setting 0, minimum unit 0.1kW
Discharge Power (kW) Set the maximum discharge power of the battery Minimum setting 0, minimum unit 0.1kW
Power-on activated Batt enable Enable and power on to activate the battery Open/Close
Active Batt Enable Activate the battery continuously after enabling Open/Close
Charge Enable After enabling, the battery can be charged (1. Direct charging with PV; 2. Preconditions for grid charging) Open/Close
Grid-tie Enable After enabling, the machine and battery are connected to the grid (a prerequisite for battery connection) Open/Close
Batt Grid-tie Enable After enabling, the main grid switch is also enabled, and the machine battery can be connected to the grid Open/Close
AC Charging Max current (A) Set the maximum charging current of the battery to the mains power supply Minimum setting 0, minimum unit 1A
AC charging target SOC (%) Set the SOC for charging the battery using mains power Minimum setting 0, minimum unit 1%
AC charging target Volt (V) Set the voltage for charging the battery using mains power Minimum setting 0, minimum unit 0.1V
Battery capacity (Ah) Set according to the actual installed battery capacity Minimum setting 0, minimum unit 1Ah
Lithium battery loss report fault switch After setting, if the battery BMS cannot communicate with the inverter, the inverter will stop working and report a fault Open/Close
Discharge Cut-off Volt (V) When the battery voltage is below this set threshold, the battery cannot generate electricity Minimum setting 0, minimum unit 0.1V
Recovery Volt (V) When the battery voltage exceeds the threshold set, the battery can be discharged Minimum setting 0, minimum unit 0.1V
Discharge Cut-off SOC (%) After setting the value, the battery will stop discharging when the SOC is lower than the set value Minimum setting 0, minimum unit 1%
Recovery SOC (%) After setting the value, the battery will resume discharging when the SOC is higher than the set value Minimum setting 0, minimum unit 1%
Chai Fa Charging Switch After setting up, use a generator to charge the connected battery pack Open/Close
Diesel charging current (A) Can set the generator to charge the battery current Minimum setting 0, minimum unit 1A
Chai Fa Signal Set the discharge power of the energy storage device. Realy normally open/Relay closure
Diesel engine forced opening When the generator is connected, it is forced to start the generator without meeting other conditions Open/Close
AC Charge Enable After setting up, use the power grid to charge the connected battery pack Open/Close
Grid Charge Activation Volt (V) When the battery voltage falls below this set threshold, the power grid begins to forcefully charge the battery Minimum setting 0, minimum unit 0.1V
Grid Charge Activation SOC (%) When the SOC of the battery falls below this set threshold, the power grid begins to forcibly charge the battery Minimum setting 0, minimum unit 1%
Grid charging current (A) Can set the charging current of the battery to the power grid Minimum setting 0, minimum unit 1A
Power grid signal Set the discharge power of the energy storage device. Minimum 0, minimum unit 0.1kW
Float Volt (V) Set the float charging voltage for lead-acid batteries Minimum setting 0, minimum unit 0.1V
Absorption Volt (V) Set the constant voltage charging voltage for lead-acid batteries Minimum setting 0, minimum unit 0.1V
Balanced charging voltage (V) Set the balanced charging voltage for lead-acid batteries Minimum setting 0, minimum unit 0.1V
Balanced charging cycle (days) Set the balanced charging cycle for lead-acid batteries Minimum setting 0, minimum unit 1Day
Balanced charging duration (hours) Set the balanced charging duration for lead-acid batteries Minimum setting 0, minimum unit 1 hour
Under voltage alarm voltage (V) Alarm lead-acid and lithium batteries when they reach the set voltage value Minimum setting 0, minimum unit 0.1V
Under voltage alarm SOC (%) Alarm lead-acid and lithium batteries when they reach the set SOC value Minimum setting 0, minimum unit 1%

# Energy Management

Parameter NameParameter DescriptionParameter Range
Energy allocation mode Select inverter operating mode Off-grid Mode
UPS Mode
Self-generating-and-use Mode
Peaking shift Mode
Electricity sales mode
Internal CT anti backflow
External CT anti backflow
Forced Charging time setting The machine works according to the set parameters such as the forced charging time period
AC Charging After being turned on, the power grid can charge the battery Open/Close
AC Charging time setting The machine works according to the set parameters such as AC charging time period
Charge/Discharge time setting in Peaking shift Mode The machine works according to the set parameters such as peak shaving charging or discharging time period
PV energy supply priority setting Set the priority of energy flow for photovoltaic power generation Load - Battery - Grid
Load-Grid-Battery
Battery - Load - Grid Connection
Peak shaving of power grid Enable the grid peak shaving function after activation Open/Close
Peak shaving power of power grid (W) Limit the power supply from the power grid Minimum setting 0, minimum unit 1kW
Zero output power (W) Output power to the grid is zero Minimum setting 0, minimum unit 1kW
Timed charging and discharging After setting up, support the power grid or generator to charge the battery, and when the battery discharges to supply power to the load Open/Close
Charging and discharging time setting The machine charges or discharges the battery according to the set charging and discharging time period

# Remote Maintenance

Parameter NameParameter DescriptionParameter Range
ON/OFF Default enable, i.e. power on state, disable to enter standby state Power on/off
Restart After enabling, the machine will restart Open/Close
Measurement Selection Set according to the actual time in the country/region where the device is located Nothing
Meter
CT
CT Auto-Test Enable After enabling, the CT direction can be set Open/Close
R.CT direction setting After enabling, perform reverse connection judgment under the condition of battery grid connection. If there is an abnormality, an error message will be given, and the correct CT direction can be manually set Normal/Reverse
S.CT direction setting After enabling, perform reverse connection judgment under the condition of battery grid connection. If there is an abnormality, an error message will be given, and the correct CT direction can be manually set Normal/Reverse
T.CT direction setting After enabling, perform reverse connection judgment under the condition of battery grid connection. If there is an abnormality, an error message will be given, and the correct CT direction can be manually set Normal/Reverse
External CT transformation ratio The transformation ratio is determined by the external CT
R phase external CT enable After enabling, the CT direction can be set
Electricity meter brand and agreement The corresponding electric meter brand when connecting an external electric meter
Restore Factory After enabling, all settings of the machine are restored to factory settings Open/Close

# External devices

Alternator

Parameter NameParameter DescriptionParameter Range
Diesel engine mode setting Choose the diesel engine working mode Power generation output/Intelligent load
The smart load of the power grid is always on After setting, the smart load will be turned on when the power grid exists Open/Close
Intelligent load startup battery SOC (%) If the battery SOC is greater than this set value, start the intelligent load Minimum setting 0, minimum unit 1%
Intelligent load shutdown battery SOC (%) If the battery SOC is less than this set value, turn off the smart load Minimum setting 0, minimum unit 1%
When the power grid is disconnected, the smart load will immediately shut down When there is no power on the grid side, immediately turn off the smart load Open/Close

Heat pump

Parameter NameParameter DescriptionParameter Range
Heat pump Select the working mode of the heat pump Disable/Manual mode/Smart mode
Switch status If the function mode is selected as manual mode, it can be controlled to turn on or off, otherwise only the current output status can be read Open/Close
Feed-in power control After enabling, other enabled functions will automatically turn off, and the heat pump will operate according to the set parameters Open/Close
Feed-in power threshold(W) When the upstream power is greater than the set value, turn on Minimum setting 0, minimum unit 1W
Min operation time(min) Minimum running time after each opening Minimum setting 0, minimum unit 1 minute
Max operation time(min) Maximum daily operating time Minimum setting 0, minimum unit 1 minute
Consumption power threshold(W) When the downlink power is greater than the set value, it will be turned off Minimum setting 0, minimum unit 1W
End SOC threshold(%) When the SOC of the battery is less than the set value, it will be turned off Minimum setting 0, minimum unit 1%
Batt SOC control After enabling, other enabled functions will automatically turn off, and the heat pump will operate according to the set parameters Open/Close
Start SOC threshold(%) If the SOC of the battery is greater than the set value, open it Minimum setting 0, minimum unit 1W
Min operation time(min) Minimum running time after each opening Minimum setting 0, minimum unit 1 minute
Max operation time(min) Maximum daily operating time Minimum setting 0, minimum unit 1 minute
Consumption power threshold(W) When the downlink power is greater than the set value, it will be turned off Minimum setting 0, minimum unit 1 minute
End SOC threshold(%) When the SOC of the battery is less than the set value, it will be turned off Minimum setting 0, minimum unit 1%
Time control After enabling, other enabled functions will automatically turn off, and the heat pump will start working according to the set working time period Open/Close
Heat pump operation time Set the working time period of the heat pump so that the equipment can only work normally during the time period when it can be turned on

# Quick configuration steps

① Log in to the Smart M app.

② Click on [Device] at the bottom to enter the data list page.

③ Click the [...] - [Configure] button on the right side. (If the device model supports quick configuration, clicking the configuration button will bring up a configuration mode selection pop-up window. If quick configuration is not supported, the page will directly enter the parameter configuration page.)

④ Select Quick Configuration in the pop-up configuration mode selection window.

⑤ In the pop-up quick configuration pop-up page, select the parameter type that needs to be set.

⑥ In the corresponding parameter type input box, enter the parameter value that needs to be modified, and click the [Settings] button.

# Device self check

① Log in to the Smart M app.

② Click on [Device] at the bottom to enter the data list page.

③ Click the [...] - [Configure] button on the right side.

④ In the pop-up parameter configuration page, select the power grid parameter option. (Only machines in some regions support self checking, and the self checking button will only be displayed if the regulations are set to the corresponding region)

⑤ On the power grid parameter page, click the Automatic Detection button.

⑥ Click the Start button on the pop-up page to start the self check.

⑦ Wait for all self-test items on the detection page to complete, and the device will complete its self-test.

# Offline configuration

① Log in to the Smart M app.

② Click on the bottom [Device] to enter the data list page.

③ Find the offline devices under your Plant and click the [...] - [Configuration] button on the right.

③ Select the parameters you need to adjust, modify the content you need to modify, and click the [Create Offline Task] button.

-After clicking the "Create Offline Task" button, the device will create an offline task. When the device connects to the service again, the platform will issue the offline task to the device at a certain frequency.

# Offline task viewing and operation

  After completing the offline task creation, you can view the previously created tasks through the [Offline Tasks] button in the upper right corner of the [Parameter Configuration] page and perform operations on related tasks.

Offline task viewing

① Log in to the Smart M app.

② Click on the bottom [Devices] to enter the device list page.

③ Click the [...] - [Configuration] - [Offline Tasks] button on the right to enter the offline task page.

Offline task operation

① Log in to the Smart M app.

② Click on the bottom [Devices] to enter the device list page.

③ Click the [...] - [Configuration] - [Offline Tasks] button on the right to enter the offline task page.

④ Click the [...] button in the bottom right corner of offline task data to perform operations on the current task, and pause unexecuted offline tasks.